Anode erosion and electron beam energy estimates
LPP has just started sending out technical reports to supplement the monthly reports, as many would like to know the technical details. Unfortunately, this may be a bit confusing. Those not interested in the details need not read further. In general, these reports will be elaborations on points already mentioned in the monthly report.
The significance of this anode report is as follows; it is basically good news in that it shows we are converting a lot of the energy into the beam. The erosion will decrease, we expect, when the electron energy gets higher and the beam penetrates more into the copper, dispersing the energy better.
Since December, the depth of the hole that was machined into the anode, the central electrode, has been measured with a depth gauge four times. The results are shown at the end of this note. Since we have not accurately measured the length of the entire electrode—we will do this next time we open the chamber—we cannot directly measure the erosion off the lip of the electrode. But since the electrode can’t get any longer, we can estimate the minimum erosion from the times when the distance from the lip to the edge decreased. By adding this to the measured increase in the depth of the hole, we can estimate a minimum rate of erosion. This turns out to be about 18 microns per pinch. If we assume the beam is only exactly as wide as the hole—a ride of 1.4 cm (it may be somewhat larger), the minimum amount of erosion per pinch is 0.011 cc or 0.1 gm of copper. To raise this much copper to vaporization temperature and then boil it takes 570 J of heat. Some copper could be removed by melting, forming droplets and the droplets falling off the surface, which is pointed downwards. However, other copper was surely heated far above its boiling point by high energy particles, so this energy estimate is still conservative. Since the ion beam must contain the same energy, the average pinch contains 1.1 kJ. For comparison, the energy in the magnetic field, assuming an inductance of about 5 nH, is 1.2 kJ for a peak current of 700kA. The kinetic energy of the plasma should be similar for a total available energy of 2.4 kJ.
Is it reasonable that the e-beam is depositing so much energy in the anode surface? The depth of penetration of an electron is 0.1 E1.5/p microns, where E is electron energy in keV and p is density. So a penetration of 18 microns would mean average electron energy of 140 keV. Of course one could have higher energies, spread out over a greater depth, but with more energy.
From the total energy estimate and the electron energy, we can get an estimate of 4 mC for the total charge in the beam. If we then assume that the beam is spreading out linearly and covers a 1.4 cm radius circle at a distance of 4 cm, we can expect that at the upper Rogowski coil, we will get a total charge passing of 0.28 mC. Interestingly, while we are still working on getting the noise down in the beam Rogowski coil, one seemingly clear signal from shot 040209 did contain 0.13 mC, not far from our estimate. While we can’t be sure this is not noise until we get both beam Rogowskis working and their noise down, this particular pulse would have originated at about the same time as an X-ray pulse observed by the Far Time of Flight (or FTF) instrument.
Observations (distances in inches):
Hole radius: 0.55, half-radius: 0.27
Original depth of anode hole: 1.575
Dec 12 – edge 1.568, center 1.587, center erosion 0.012, total >0.019, 18 pinches
Feb 12 – edge 1.565, half 1.580, center 1.591, center erosion 0.04 total >0.07, 10 pinches
Mar 22 – edge 1.593 half 1.595 center 1.609 center erosion 0.018 center-half 0.003, 25 pinches
Apr 1 – edge 1.581 half 1.581 center 1.597 center erosion 0 center-half 0.002 total >0.014, 18 pinches
Average erosion per pinch – 0.0007 inch/pinch
Lip erosion > 0.022”
Edge erosion > 0.050”
Half erosion > 0.050”
Center erosion >0.066”
Assume beam radius is 0.55”, 20 degrees
18 microns penetration of electrons into copper
0.011 cc of copper vaporized
0.1 gm of copper vaporized
569 J heat of vaporization plus heating to boil for copper
E-beam width about 20 degrees
Plasmoid minimum energy 1.1 kJ
Total magnetic energy at 0.7 MA: 5 nH, 1.2 kJ, total energy 2.4 kJ


(9) Comments
More on Magnetic Fields
April 28 Panel Dicussion at UTS in NYC with Eric Lerner










Comments
For a more in depth discussion, start a thread in the forums.Since nearly everything is in SI units, why use inches? I, at any rate, would prefer mm for things like erosion, etc. thanks.
jj;
So they can say “inch/pinch”!
What is the maximum tolerable erosion to have an adequate electrode lifetime?
Where can we find the monthly reports and technical reports?
I know that most people won’t understand most of it (including myself), but for those observers who are in the plasma physics community, it makes the world of difference in the ability to evaluate the current status of the experiments - which is of course very important continuing to garner support.
I’ve searched around and while I’ve seen several old reports, I don’t see a stream of “technical reports” or “monthly reports” searching in any of the obvious places.
That kind of erosion is clearly going to have to eventually be cut down by lotsa orders of magnitude. At that rate, you’d be digging a 1” hole every 5-6 seconds at full operating levels (330Hz). And vaporizing about an ounce of copper!
Is electrode erosion a show-stopper? Many have suggested so.
Frogman;
I think the “sending out” Eric is referring to is mailings to the members. I’m not a paid member either (poverty and all that jazz), but the copying of those reports to the LPP and FFS sites seems to be getting more organized.
Become a member, and/or keep scouring the Home Page like me!
Assuming electrode lifetime of 90 days, and it can erode no more than x µm in that time before it becomes useless, and a rate of 330 pinches/s full duty (that’s 2.56e9 pinches in 90 days), so max erosion = x/2.56e9 µm each pinch. if x = 1000, then it turns out that max erosion each pinch is on the order of a thousanth of a single layer of atoms at the surface.
Actually, no linear extrapolations can be made, apparently. Eric emailed me a while ago and said, “I expect erosion to go way down once most of the ebeam energy is absorbed by the plasmoid. Stay tuned and be patient!” & [beam absorption] “is an exponential decay, less plasmoid, less beam, vice versa.”
I take it that it is pointless to worry about the issue in the absence of data at the higher energy levels.
yes, no linear extrapolations from current to future erosion (per pinch) can be made, since soft x-rays erode more than hard x-rays, due to the fact that they absorb closer to the surface. but the bounds i calculated are valid regardless.
Post a Comment